? Want steady water pressure from every faucet and fixture in your home without the pump cycling on and off every few minutes?
What is a constant pressure system?
A constant pressure system keeps your water pressure steady regardless of how many fixtures are running. Instead of relying on a traditional pressure tank and pressure switch that cycles the pump on and off, these systems use an electronic controller (usually a variable frequency drive or VFD) and a pressure sensor to vary pump speed so pressure remains constant.
You’ll notice smoother performance, longer pump life, and fewer pressure spikes. Constant pressure systems are commonly used with submersible well pumps but can also be applied to surface or jet pumps.
How constant pressure differs from traditional systems
Traditional systems use a pressure tank to store water and a pressure switch to turn the pump on at a low pressure and off at a high pressure (for example, on at 30 psi, off at 50 psi). That cycling produces pressure fluctuations and frequent starts.
Constant pressure systems modulate pump speed so the pressure stays at your set point regardless of flow. The pump may run more continuously but at lower stress levels due to soft starts and fewer starts/stops.
Why choose a constant pressure system?
You’ll see these main benefits:
- Consistent water pressure at every tap, even during simultaneous use (showers + dishwasher + outdoor hoses).
- Smoother pump operation with fewer starts and stops, which can extend pump life.
- Energy savings in many cases, since the pump runs at lower speeds when demand is low.
- Elimination of large pressure tanks in many installations, saving space and maintenance.
If you need steady pressure for irrigation, multiple bathrooms, or an RV/home hybrid, a constant pressure system can be a big upgrade.

Types of constant pressure systems
Constant pressure can be achieved in several ways. You’ll choose the method that matches your existing pump type, power availability, and budget.
- VFD/Inverter on submersible pumps: A VFD controller varies the frequency to the pump motor, changing pump speed to maintain pressure. This is the most common for deep well submersible pumps.
- Soft-start controllers with pressure transducer: For smaller pumps, a controller adjusts motor speed and provides soft starts without a full VFD.
- Multi-stage controllers or frequency converters for surface/jet pumps: Adaptations exist for above-ground pumps.
- Hydropneumatic systems with a variable-frequency controller: Use a smaller pressure tank as a buffer to reduce very short-term cycling.
Use the table below to compare common configurations:
| System type | Best for | Typical benefits | Drawbacks | 
|---|---|---|---|
| VFD on submersible pump | Deep wells with submersible pumps | Excellent pressure control, energy efficient, reduces cycling | Higher upfront cost, requires proper setup | 
| Soft-start controller + transducer | Smaller single-phase pumps | Reduced inrush current, smoother starts | Less precise pressure control than VFD | 
| VFD on surface/jet pump | Shallow wells or booster pumps | Good control, saves energy | Requires compatible pump and motor | 
| Small pressure tank + controller | Retrofit where tank elimination isn’t desired | Shortens cycling, provides buffer | More components, still some cycling | 
Components you’ll need
You’ll need pump-specific parts, electrical components, plumbing supplies, and tools to complete the installation.
Here’s a table listing common parts and tools:
| Category | Item | Notes | 
|---|---|---|
| Pump hardware | Submersible pump (existing or new) | Confirm motor compatibility with VFD if using one | 
| Controller | VFD / constant pressure controller | Sized to pump voltage, phase, and HP; IP-rated enclosure if outdoors | 
| Sensor | Pressure transducer / pressure sensor | 4–20 mA or 0–10V output for controller compatibility | 
| Plumbing | Check valve, isolation valves, union, pressure relief valve | Use brass/stainless for durability | 
| Electrical | Circuit breaker / fused disconnect, conduit, motor cable, grounding rod/kit, surge protector | Follow local code | 
| Auxiliary | Pressure tank (optional), bladder tank (optional) | Small buffer tanks reduce pump response frequency | 
| Tools | Pipe wrenches, tubing cutters, multimeter, clamp meter, drill, thread sealant | Include personal protective equipment | 
| Consumables | Teflon tape, thread compound, cable ties, cable clamps | Use water-rated materials | 
Notes on selecting components
- Match the VFD to the pump motor’s full-load amperage, voltage (e.g., 230V single-phase, 230/460V three-phase), and horsepower.
- Pressure transducers come in ranges (0–100 psi, 0–200 psi). Pick one that covers your desired working pressures.
- Use motor cable rated for submersible service when running down into a well; standard building wire is not suitable.
- Use a fused disconnect near the pump controller as required by code.

Planning and sizing your system
Good planning prevents costly mistakes. You must determine flow needs, pump head, pump motor size, and electrical requirements.
Step 1 — Determine your flow (GPM) needs
Estimate how much flow you’ll need when multiple fixtures run. Use typical values:
| Fixture | Typical GPM | 
|---|---|
| Toilet (tank fill) | 1–2 | 
| Shower | 1.5–3 | 
| Kitchen sink | 1–2 | 
| Washing machine | 2–3 | 
| Dishwasher | 1–2 | 
| Hose for irrigation | 5–10 | 
Add up simultaneous flows to get peak demand. For a family home with two bathrooms, 8–12 GPM is a common target. For irrigation or multiple bathrooms, expect 15–30+ GPM.
Step 2 — Calculate total dynamic head (TDH)
TDH = vertical lift (static head) + friction loss + pressure head.
- Static head: difference between pump setting and highest draw point (feet).
- Pressure head: convert desired pressure (psi) to feet (1 psi ≈ 2.31 feet). For 50 psi, pressure head = 50 × 2.31 = 115.5 feet.
- Friction loss: depends on pipe length, diameter, fittings, and flow. Use friction loss charts or calculators.
Example: static head 50 ft + pressure head 115.5 ft + friction 10 ft = TDH ≈ 175.5 ft.
Step 3 — Select pump based on pump curve
Match required GPM and TDH with the pump’s performance curve. The pump must be able to deliver the required flow at the computed TDH.
If considering a VFD, the pump should not operate much to the left of the curve where it may overheat at very low flows. Consult manufacturer charts.
Step 4 — Electrical sizing
- Determine voltage and phase available at your site.
- Find pump motor full-load amperage (FLA) and select a VFD/disconnect and breakers accordingly—VFDs must handle inrush and continuous loads.
- Calculate wire gauge based on ampacity and distance; account for voltage drop. For long cable runs, larger conductors may be needed.
Step 5 — Pressure setpoints
Decide on target pressure (commonly 45–60 psi) and minimum/maximum values. The VFD will maintain this setpoint; you’ll also set alarms for over/under pressure.
Safety, codes, and permits
You must follow electrical and plumbing codes. Local jurisdictions often require permits for well work and electrical changes.
- Electrical code: A licensed electrician should handle high-voltage wiring and breaker sizing, and ensure proper grounding and bonding.
- Plumbing code: Backflow prevention and cross-connection controls may be required.
- Well code: Work on wellheads and equipment may require licensed well contractors.
- Permits: Check with your local building department before starting. Improper installations can void warranties or create hazards.
Always de-energize circuits before working. Use lockout/tagout practices if available. If you’re not comfortable with electrical work or well construction, hire a qualified pro.

Step-by-step installation
This section outlines a typical installation of a constant pressure VFD-controlled system for a submersible well pump. Adjust steps if you have a surface pump, jet pump, or different configuration.
Preparations
- Obtain necessary permits and inspect local code.
- Gather tools, parts, spare fittings, and PPE.
- Turn off power to the pump at the main panel and disconnect the pump from the circuit.
- Remove the well cap and carefully lift the pump (if replacing pump or bringing cable up). If retrofitting controller only and not pulling pump, proceed with caution.
Mounting the VFD/controller
- Mount the VFD in a dry, ventilated location near the pressure plumbing and electrical access. Ensure proper spacing per manufacturer instructions for cooling.
- If outdoors, use an IP-rated enclosure or place the VFD in a weatherproof cabinet.
- Install a fused disconnect or breaker between the main panel and the VFD per code.
- Provide surge protection on the power lines feeding the VFD to protect electronics from lightning or grid surges.
Installing the pressure transducer and plumbing
- Install the transducer on the pressure side—after the pump or in the pressure line near where you want to control pressure. Use a T-fitting or port provided in your piping layout.
- Install isolation valves on either side of the transducer for convenient service.
- Install a check valve and isolation valve near the wellhead to prevent backflow and allow servicing.
- If you use a small pressure tank, install a tee and bladder tank at the pressure line with a pressure gauge.
Wiring the pump and controller
- Use NSF/UL-rated submersible pump cable and connect to the motor using a proper splice or motor lead termination in the well cap or control box.
- Run motor cable through conduit with proper support and secure it near the controller.
- Connect motor leads to VFD output terminals (U, V, W for three-phase; follow VFD manual for single-phase to three-phase solutions if applicable).
- Connect the VFD input to the fused disconnect and breaker.
- Connect the pressure transducer to the VFD or controller input per the voltage/current signal type (4–20 mA or 0–10V).
- Connect ground/earth to the VFD and to the motor cable. Ensure a continuous grounding path to the grounding electrode system.
Programming and initial startup
- Program the VFD for motor nameplate values (voltage, full-load amps, motor frequency, and poles).
- Set pressure setpoint, minimum and maximum frequency limits, acceleration/deceleration times, and any pump protection parameters (overcurrent, underload, dry-run).
- With isolation valves closed and the system blocked, energize the VFD and run a short test to verify rotation and motor direction (if reversible). For submersible motors, you can verify direction via current balance or manufacturer guidance.
- Open the isolation valves, then initiate a controlled run in manual or test mode to fill the lines slowly and release air.
- Observe pressure transducer readings and confirm the controller adjusts motor speed to reach and hold the setpoint.
Final checks
- Check for leaks at joints and fittings.
- Verify check valve operation.
- Confirm that the pump does not overheat and that the VFD’s cooling fans are operational.
- Record initial operating amperage and system pressures for future reference.
- Label wires, valves, and the controller for service clarity.
Setting pressure setpoints and tuning
You’ll configure the controller to maintain a set pressure. Basic tuning parameters:
- Setpoint pressure: The pressure you want the system to hold (e.g., 50 psi).
- Pressure transducer span and scaling: Ensure the controller reads 0–100% for the transducer range.
- Deadband or hysteresis: Defines small allowable pressure variation around the setpoint before the controller adjusts speed. A narrower deadband gives tighter control but can increase pump frequency changes.
- Minimum frequency: Prevents the motor from operating at speeds where overheating or poor cooling might occur.
- Maximum frequency: Matches motor design and ensures you don’t over-speed the motor.
- Ramp (accel/decel) times: Soft starts and stops reduce mechanical stress and water hammer.
Typical starting values:
- Setpoint: 50 psi
- Deadband: ±1–2 psi (or let the controller maintain precisely at setpoint)
- Min frequency: 20–30% of rated frequency (to ensure adequate motor cooling)
- Accel/decel: 3–10 seconds for smooth response
Fine-tune based on actual system behavior. If pressure oscillates, increase deadband or slow down response (longer ramp times). If pressure lags during high demand, consider increasing acceleration or allowing a short higher-frequency boost.

Commissioning and testing
After installation and initial programming, thoroughly test the system.
- Simulate different demand scenarios: single faucet, simultaneous showers, irrigation on, and maximum expected flow.
- Watch pressure response and verify the VFD adjusts speed smoothly.
- Measure amperage to ensure the motor runs within full-load amp ratings.
- Check temperatures at the motor and VFD after extended operation.
- Verify alarms for high/low pressure and pump faults.
Record all readings. If anything is out of range, power down, inspect, and reconfigure.
Troubleshooting common issues
Here’s a troubleshooting table for common symptoms and remedies:
| Symptom | Possible cause | What you can do | 
|---|---|---|
| Pump won’t start | Power off, tripped breaker, faulty disconnect, VFD fault | Check main breaker, disconnect fuse, VFD fault code; reset after fixing cause | 
| Pressure spikes or oscillation | Controller tuning too aggressive, transducer noise | Increase deadband, smooth response by lengthening accel/decel time; check transducer wiring | 
| Low pressure under flow | Pump can’t deliver required flow at TDH | Re-check pump curve vs TDH; consider larger pump or parallel pumps | 
| VFD overheating | Poor ventilation, high ambient temp, overcurrent | Improve ventilation, install in cooler location, check sizing | 
| Rapid cycling or surges | Undersized check valve, leak, bad transducer | Replace check valve, pressure test lines, calibrate transducer | 
| Motor draws excessive current | Blocked impeller, wrong motor wiring, pump jam | Inspect pump, verify wiring and phase rotation, check for debris | 
| Water hammer / pressure spikes | Sudden pump stops, fast valve closures | Add small pressure tank or soften decel time on VFD | 
If you encounter persistent faults or VFD error codes you don’t recognize, consult the VFD manual or the manufacturer’s tech support.

Maintenance
Regular maintenance keeps your constant pressure system reliable.
- Quarterly: Inspect electrical connections, check for corrosion, verify transducer accuracy, look for leaks.
- Annually: Test motor amperage, inspect and exercise all valves, check check valve operation, service or replace pre-filters or strainers.
- Every 3–5 years: Inspect the pump (if you can), replace worn bearings or seals, or plan for professional inspection.
- After storms or electrical events: Verify the VFD and surge protection are intact.
If your system includes a small pressure tank, check its air charge and bladder integrity.
Costs and timeline
Costs vary based on pump size, controller features, and whether you hire a pro. Typical ranges:
| Item | Approximate cost (USD) | 
|---|---|
| VFD / constant pressure controller | $400–$2,500 | 
| Pressure transducer | $50–$250 | 
| Installation materials (valves, check valve, wiring) | $100–$600 | 
| Pump (if replacing) | $500–$2,000+ | 
| Labor (licensed electrician/well tech) | $500–$2,000+ | 
| Permits and inspections | $50–$500 | 
For a standard home retrofit using your existing pump and hiring professionals, budget $1,500–$4,500. Replacing a pump and installing a VFD may push costs higher. DIY installations can reduce labor but require electrical expertise and strict adherence to code.
Timeline:
- Planning and permits: a few days to a few weeks.
- Physical installation (professionals): 1–2 days typically.
- Commissioning and tuning: a few hours.
When to call a professional
You should hire a professional if:
- You’re not licensed for well or electrical work.
- You need to replace or pull a submersible pump.
- Your electrical panel can’t support the new load.
- You suspect well contamination, structural issues, or low well yield.
- Local regulations require licensed installers.
Professionals can size the pump and controller precisely, pull motors safely, and ensure code compliance.
Frequently asked questions (FAQs)
Can I install a constant pressure controller on a single-phase pump?
Yes, many controllers are made for single-phase pumps. However, VFDs for single-phase motors are less common, and some VFDs will accept single-phase input and provide three-phase output (or use soft-start controllers). Match the controller to your motor type and consult the manufacturer.
Do I still need a pressure tank?
Not always. VFD systems often eliminate the need for large pressure tanks because the controller smooths pressure. Some installations use a small buffer tank to reduce short-term fluctuations and protect the pump from very short duty-cycles.
How does the pressure transducer get calibrated?
Transducers usually come pre-calibrated. When installed, you’ll configure the controller to read the transducer span (e.g., 0–100 psi) and map it to the controller’s setpoint values. Follow the controller manual for exact steps.
Will a constant pressure system save energy?
Often yes, especially if your previous system started the pump frequently at full speed. By running the pump at reduced speeds during low demand, a VFD often reduces energy consumption. Savings depend on duty cycle and pump sizing.
Is my well suitable for a constant pressure system?
Most wells with submersible or surface pumps can be adapted, but low-yield wells may not support continuous operation at flow rates needed for constant pressure. If your well has limited drawdown or long recovery times, consult a well professional.
Final thoughts
Installing a constant pressure system for your well can transform your water experience by providing steady pressure, quieter operation, and potentially lower energy costs. With careful planning—measuring flow needs, calculating total dynamic head, selecting compatible components, and following code—you can either retrofit your existing system or install a new, modern solution.
If you’re comfortable with plumbing and low-voltage electrical wiring and your local code allows, you can tackle some retrofit tasks yourself. For anything involving high-voltage wiring, motor work, wellhead modifications, or pump pulls, you should engage a licensed electrician and/or well contractor to ensure safety and compliance.
If you want, tell me the details of your well (pump type, motor voltage/HP, distance to service panel, and your household’s peak GPM), and I can help you estimate TDH, suggest suitable controller sizing, and outline a parts list specific to your setup.
